Specific Parameters Of Our Mining Containers
The values in the table below are the CSA certified values. The certified values are lower than the actual values because the CSA has set the security values.
Configuration List
The Specification of Ore Box- RUISU-1200 Mining Enclosure
Model | Ore Box- RUISU-1200 Mining Enclosure
|
|
Dimensions | Enclosure Length x Width x Height | Length: 37.73 (feet) x Width: 7.22 (feet) x Height: 7.74 (feet) |
Number of installed mining rigs | 336 units with 3.25kW up to 4.0kW power consumption per rig
|
|
Enclosure rating
|
NEMA 3 / IP54
|
|
Power
Power |
Power Input KW
|
Upper Limit: 1,354 KW
|
Input Voltage
|
380 – 415VAC 3ph
|
|
Inside Access
|
3 phase power connection to inside access 4 Main Breakers
|
|
Connection type
|
3 phase wires, 1 Neutral, 1 Ground, each phase Volts: 380-415VAC / 220-240VAC
|
|
Distribution Panel and Breakers
|
Each cabinet has 4 power distribution panel. Each distribution panel: 1 x 630A 3-pole molded case main circuit breaker, 4 x 175A 3-pole molded case circuit breaker, 84 x 20A 1P circuit breaker, 4x6A 3P circuit breaker, 1x10A 2P circuit breaker, 3x20A 2P circuit breaker, 1x32A 4P circuit breaker, 1xSPD 40 (3L+N) surge protector
|
|
Power Distribution & Cabling
|
1. Power distribution unit: main panel circuit breaker (Schneider), distribution circuit breaker (Nader), contactor (Nader).
2. Equipment and rack: Ore Box installation rack, UL standard Ore Box power socket, lighting, cooling fan, Water curtain. 3. All wiring: use cable (mining cable UL1015 10/12/14 AWG) Including the outlet from the circuit breaker of the distribution panel to the power socket of the miner, the Y-type pigtail can be ordered separately to connect the dual miner plug input to the power socket. The lighting and cooling fans are installed in the container and can be used directly. |
|
Cooling | Cooling technology
|
Air Economizer with Evaporative cooling, 8 Panels per Container
|
Industrial grade Exhaust Fans (370W per fan)
|
16 Fans with automated louvers (With CSA certification)
|
|
Fans blade diameter | 850 mm | |
Fan blade revolving speed | 450 (r / m) | |
Fans input power | 0.37 KW | |
Fans rated Voltage | 380 V | |
Air flow (Cubic-Feet-per-Minute)/(per fan)
|
15,891.6 CFM (15,891.6 Cubic Meter/Hour)
|
|
Fans dimension(Height x Length x Width) | 900 x 900 x 350 (mm) | |
Total Air flow in Container /(CFM)
|
254,266 CFM (254,266 Cubic Meter/Hour)
|
|
Air filtering system
|
Include air filter net and dust filter net | |
Additional technical details | Security | Key locks standard to dual entry/egress security doors
|
Regulatory compliance | UL 489, Compliant to IEC 60950 and international wiring regulations
|
|
External Environmental Operation limits | Operating temperatures | 40°F to 115°F
|
Operating humidity range | 0 to 90% RH (below Condensation point)
|
|
Operating altitude | 0 to 5,000 ft
|
|
Spacing distance requirements | Power distribution cabinet to mining rigs rack | The distance between the power distribution cabinet and mining rigs rack can be 1.04 M |
Socket installation rack to water curtain | The distance between the socket installation rack and water curtain position can be 1.1 M -1.2 M |
Feature:
- The Ore box container is safe and firmly meets the CUL certification standards.
- The whole container of electrical parts (including cable, socket, fan, etc.) ,all are passed UL certification.
- The fire exit meets the certification standard (safe escape lock is used when opening the door on the opposite side).
- The whole container has passed the protection safety test and reached the certification standard.
- The whole container of electrical equipment has passed the load test and meets the certification standards.
- The whole container has passed the rain test and reached the certification standard.
- We can make customized solutions for customers, and make a power distribution system with corresponding standards in accordance with the local market.